Basic Info.
Model NO.
PR-12DC-DA-R-N
Supply
DC 24V
Weight
Approx. 300g
Expansion
Yes(16PCS in Max)
Transport Package
Standard Export Carton
Specification
95mm*90mm*61mm
Trademark
RIEVTECH
Origin
Nanjing, China
HS Code
8537101190
Product Description
Ethernet PLC
Simple panels, easier to integrate into your equipment
Built-in Web Server
With embedded configurable sensor
The built-in RS485 interface makes communication more convenient
Support for MQTT protocol, data access to the IoT cloud service directly
Specific characteristics
Module | PR-12AC-R-N | PR-12DC-DA-R-N |
Input | I1--IC: 8DI(AC) | I1--I4 : 4DI/AI (0--10V signal) I5--I8 : 4DI/HSI |
Output | Q1--Q4 ( RELAY 10A 250VAC /5A 30VDC) | |
Supply | AC 110~240V | DC 24V |
Weight | Approx. 350g | Approx. 300g |
Dimensions | Without packing: 95mm*90mm*61mm With packing: 107mm*96mm*73mm | |
Expansion | YES(16PCS in max) |
General characteristics
Products certification | CE |
Conformity with the low voltage directive (in accordance with BT 2006/95/EC) | IEC/EN 61131-2 |
Conformity with the EMC directive (in accordance with 2004/108/EC) | IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments) IEC/EN 61000-6-2 (Industrial) IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments) IEC/EN 61000-6-4 (Industrial) |
Protection rating | In accordance with IEC/EN 60529: IP20 |
Overvoltage category | 3 in accordance with IEC/EN 60664-1 |
Mechanical resistance | Immunity to vibrations IEC/EN 60068-2-6 Immunity to shock IEC/EN 60068-2-27 |
Resistance to electrostatic discharge | IEC/EN 61000-4-2 Severity 3 |
Resistance to HF interference | Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Severity 3 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12 |
Conducted and radiated emissions | Class B in accordance with EN 55022 |
Operating temperature | -25 ~ +55°C in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2 |
Storage temperature | -40 ~ +70ºC in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2 |
Relative humidity | 10 ~ 95 % . (no condensation or dripping water) in accordance with IEC/EN 60068-2-30 |
Mounting | On 35 mm standard mounting rail, 4 MW, or wall-mounting |
Screw terminals connection capacity | Flexible wire with ferrule 1 conductor: 0.25 to 2.5 mm2(AWG 24 ~AWG 14) |
Processing characteristics
Module | PR-12AC-R-N | PR-12DC-DA-R-N |
Program size function blocks (FBD) | 512 function blocks | |
Memory size function blocks (FBD) | 32K | |
LCD display | 4 lines of 16 characters and configurable backlighting | |
Programming method | Function blocks | |
Program memory | Flash EEPROM | |
Back-up time in the event of power failure | Program and settings in the controller: 10 years Program and settings in the plug-in memory: 10 years Data memory: 10 years | |
Cycle time | FBD: typ. 0.6ms ~ 8.0ms | |
Response time | Input acquisition time: + 1 to 2 cycle times | |
Clock data retention | 25°C typ. 20 days | |
Clock Drift | typ. ± 2 s/day | |
Timer block accuracy | time base :s(Second) Resolution : +10 ms time base :m(Minute) Resolution: +1 s time base :h(Hour) Resolution: +1 min | |
Start up time on power up | Typ. 4s |
Technical Index
Module | PR-12AC-R-N | PR-12DC-DA-R-N |
Supply | ||
Nominal voltage | 110 ~ 240 V ac | DC 24V |
Operating limits | 85 ~ 265 V ac | DC 20.4-28.8V |
Supply frequency range | 47 ~ 63 Hz | NO |
Max. absorbed power | 49 mA (85V ac) ; 37 mA (265V ac) | 2.1W (10.8V dc) 2.8 W (28.8V dc) |
Isolation voltage | 1780V ac | None |
Inputs | ||
Input voltage | 110 ~ 240 V ac | DC0-28.8V |
Input current | 0.08 mA ; 85 Vac 0.25mA ; 265 V ac; | 0.4mA ; 10.8V dc 0.5mA ; 12.0 V dc 1.2mA ; 24 V dc 1.5mA ; 28.8 V dc |
Resolution Ratio (Analog Input) | None | 0.01V (0~10v) |
Accuracy at 25 °C (Analog Input) | None | ±0.02V |
Logic 1 voltage threshold | >79 VAC; >0.06mA | > 8 VDC;>0.3mA |
Logic 0 voltage threshold | < 40 VAC | < 5 VDC;<0.1mA |
Input Response Time | Delay time at 0 to 1: 120V AC :Typ. 50 ms 240V AC:Typ. 30 ms Delay time at 1 to 0: 120V AC :Typ. 90 ms 240V AC:Typ.100 ms | Delay time at 0 to 1: I1--I4:Typ. 2.5 ms I5--I6:Typ. 1.5 ms Delay time at 1 to 0: Typ. 1.5 ms |
Maximum counting frequency | Typ.:4 HZ | Typ.:4 HZ; HSI: 60kHZ(I5--I8) |
Sensor type | Contact or 3-wire PNP | |
Input type | Resistive | |
Outputs | ||
Rated voltage | AC 250 V / DC 30 V | |
Rated current | AC 250 V: 10 A DC 30 V ; 5A | |
Electrical durability Expectancy | 105 Operations at Rated Resistive Load | |
Mechanical life | 107 Operations at No Load condition | |
Response time | Operate Time : 15 mSec. Max. Release Time : 10 mSec. Max. | |
Frequency (Hz) | resistive load : 2 Hz inductive load : 0.5 Hz | |
Communication ports parameters: | ||
COM0_TTL port | COM0 : optional RS232/RS485 (via accessories :RS232 CABLE/PRO-RS485) Band Rate:4800;9600;19200;38400;57600;115200 Communication Protocol:MODBUS RTU;MODBUS ASCII |
Ext RS485 | COM1: optional RS485 (Via PR-RS485 expansion module) Band Rate:4800;9600;19200 Communication Protocol:MODBUS RTU;MODBUS ASCII |
Built-in RS485 | COM2: Built-in RS485 Band Rate:4800;9600;19200;38400;57600;115200 Communication Protocol:MODBUS RTU;MODBUS ASCII |
Ethernet port: | Built-In(10M/100M), 1.Can be used as program or communication 2.Can be used as modbus master or slave Communication Protocol:MODBUS TCP RTU ;MODBUS RTU |
Monitoring webserver page | Yes |
Xlogic<--->Xlogic(by Ethernet) | 1 xlogic works as tcp server can connect with 8 tcp client xlogics or other tcp devices. |
Xlogic<--->Ethernet/Internet: | 1 xlogic works as TCP clients can connect with 8 different tcp servers separately in maximum |
Notes:
1.Ethernet interface configuration software is " DeviceManager for Ethernet CPU".
2.Programming software is eSmsConfig.